Skip to content
 |  Tyco Electronics Segment Indicator  |   | 
Tyco Electronics - Our commitment. Your advantage.
Visit www.tycoelectronics.com Corcom Products
Home > Series > PEM > GGHG

GG / HG Series

Smallest Filtered Power Entry Modules with Metric Fuseholders

UL Recognized
CSA Certified
VDE Approved

Catalog Data Sheet

GG / HG Series

GG Series

The GG series power entry modules combine the functions of a general purpose RFI filter with an IEC power cord connector and single or dual metric fusing, in the smallest possible panel space. A choice of .250” terminals or wire leads is available for the load-side terminations.

For maximum cost effectiveness, 6 amp models should be used for all applications rated 6 amps or less, unless the higher performance of the 3 amp models, or the much higher performance of the 1 amp models, is needed.

Models with C-suffix additionally incorporate a ground choke1 to isolate the equipment chassis from external ground at RF frequencies.

HG Series

A medical version of our GG series, these filters offer the same compact design but reduce the line-to-ground capacitance in order to meet UL 2601 patient care requirements.

See Appendix C for more information on UL544 or UL2601 health care applications.

Note: When using the models with an IEC connector, remember that the leakage current of the companion line cord, GA400, is more significant than that of the filter - which may disqualify this line cord from use in patient care applications.

 

Electrical Schematic

GG / GS / HG

GG-C

Note 1: Depicts single fues for -1 models
Note 2: For HG delete line-to-ground capacitors

CAUTION: DO NOT ATTEMPT TO OPERATE A SINGLE-FUSED MODEL WITHOUT THE FUSE DOOR IN PLACE

Resistor location for reference only

Specifications

Maximum leakage current, each line to ground:
    HG Models GG Models
  @ 120 VAC 60 Hz 2 µA .25 mA
  @ 250 VAC 50 Hz
5 µA .42 mA
     
Hipot rating (one minute):
  line to ground 1550 VAC
  line to line 1450 VDC
     
Operating Frequency: 50 / 60 Hz
     
Rated voltage (max.): 250 VAC
     
Rated Current: 1 to 6 Amps
  * refer to part number for rating
   
Fuse (not included):

5 x 20 mm
-1 models require 1 fuse
-2 models require 2 fuses

Minimum insertion loss in dB:
Line to ground in 50 ohm circuit

Current Rating Frequency - MHz
.01 .05 .10 .15 .5 1 5 10 30

GG/GS Models
1A 12 23 29 32 41 47 50 50 55
3A - 10 15 19 30 36 48 50 53
6A - 1 4 10 16 22 36 40 50
HG Models
1A 12 23 29 32 40 40 28 22 18
3A - 10 15 19 25 26 22 21 21
6A - 4 10 14 18 18 14 14 14

Line to line in 50 ohm circuit

Current Rating Frequency - MHz
.10 .15 .5 1 3 5 10 30  

GG/GS Models
1A 1 3 14 23 41 47 50 44  
3A 1 2 11 14 25 38 44 40  
6A 1 2 10 13 23 33 39 42  
HG Models
1A 2 6 19 26 30 35 35 20  
3A 1 7 16 23 30 30 30 30  
6A 4 7 16 23 30 30 30 30  

Case Styles

GG1 / HG1

Typical Dimensions
Terminals (3) .250 Holes (2) .07 Dia.
6.35 1.8
Slot .07 x .16 Mounting Holes (2)
.126 Dia
1.8 x 4.1 3.20

Download .STP file *

 

GG8

Typical Dimensions
Wire Leads (min.) : 5.0 Wire Gauge: 18AWG
127.0
Mounting Holes (2)
.126Dia    
3.20

EGS / EHGS

Download .STP file *

* .STP files can be imported as 3D models into most CAD systems.
Files are compressed in .zip format for easy download

Recommended Panel Cutouts

For panel thickness .032 - .080 [.81-2.03]
radius: 0.138 [0.35]

Case Dimensions

Part No. A B C D E
(max.) (max.) (max.) ± .015 (max.)
± .38
EGG1-1, EGG1-2,
EHG1-2
2.15 1.13 1.29 1.417 1.76
54.5 28.7 32.8 36.0 44.7

EGG8-1, EGG8-2,
EGG8C-1, EGG8C-2
2.02 1.13 1.29 1.417 1.76
51.1 28.7 32.8 36.0 44.7

EGG1C-1, EGG1C-2 2.45 1.13 1.29 1.417 1.76
62.23 28.7 32.8 36.0 44.7

EGS1-1, EGS1-2,
EHGS1-2
2.13 1.13 1.28 1.46 * 1.42
54.0 28.7 32.5 36.0 36.1

* Max

 

Part Numbers

Click on any part number for distributor stock status and eCommerce Links. For more information refer to the Corcom Part Numbering System reference.

Part Number ¹ RFI Filter Type ² Current Rating ³ Metric Fuseholders Load Side Terminations

1EGG1-1 General Purpose 1 1 .250 [6.35] Terminals (3)
1EGG1-2 General Purpose 1 2 .250 [6.35] Terminals (3)
1EGG8-1 General Purpose 1 1 5.0 [127.0] Wire Leads
1EGG8-2 General Purpose 1 2 5.0 [127.0] Wire Leads
1EGS1-1 General Purpose 1 1 .250 [6.35] Terminals (3)
1EGS1-2 General Purpose 1 2 .250 [6.35] Terminals (3)

3EGG1-1 General Purpose 3 1 .250 [6.35] Terminals (3)
3EGG1-2 General Purpose 3 2 .250 [6.35] Terminals (3)
3EGG8-1 General Purpose 3 1 5.0 [127.0] Wire Leads
3EGG8-2 General Purpose 3 2 5.0 [127.0] Wire Leads
3EGS1-1 General Purpose 3 1 .250 [6.35] Terminals (3)
3EGS1-2 General Purpose 3 2 .250 [6.35] Terminals (3)

6EGG1-1 General Purpose 6 1 .250 [6.35] Terminals (3)
6EGG1-2 General Purpose 6 2 .250 [6.35] Terminals (3)
6EGG8-1 General Purpose 6 1 5.0 [127.0] Wire Leads
6EGG8-2 General Purpose 6 2 5.0 [127.0] Wire Leads
6EGS1-1 General Purpose 6 1 .250 [6.35] Terminals (3)
6EGS1-2 General Purpose 6 2 .250 [6.35] Terminals (3)

1EHG1-2 Medical 1 2 .250 [6.35] Terminals (3)
3EHG1-2 Medical 3 2 .250 [6.35] Terminals (3)
6EHG1-2 Medical 6 2 .250 [6.35] Terminals (3)
1EHGS1-2 Medical 1 2 .250 [6.35] Terminals (3)
3EHGS1-2 Medical 3 2 .250 [6.35] Terminals (3)
6EHGS1-2 Medical 6 2 .250 [6.35] Terminals (3)

1 Ground choke available for all general purpose models. Add suffix "C" (1EGG1C-1)
Does not include EGS models
2 General purpose filter for susceptibility applications
3 Current rating @ 120 VAC and 250 VAC
USA Customer Service: 1-800-468-2023
Corcom Products Direct: 1-847-680-7400
Germany: 49-89-6089-0
Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change.