FFD Series
The new FFD series features a range of DC feedthrough filters in current ratings from 10 to 200 amps. The FFD series is designed to meet the very stringent safety requirements of EN133200 class Y4 including the 2500V pulse test.
Filter Options / Specifications
| Capacitor ID |
Value
(nF ± 20%) |
Inductance
(nH) |
DC
Resistance
(MΩ) Max. |
| CA |
2 x 10 |
70 |
6 |
| HB |
2 x 100 |
80 |
3 |
| HD |
2 x 100 |
140 |
8 |
| NC |
2 x 470 |
90 |
2 |
| ND |
2 x 470 |
120 |
1 |
| NH |
2 x 470 |
180 |
3 |
| PK |
2 x 1000 |
240 |
2 |
| RP |
2 x 4700 |
330 |
2 |
Schematic
 |
Specifications
| Rated voltage (max.): |
130 VDC |
| |
|
| Rated Current: |
10 to 200 amps* |
| |
* refer to part number for rating |
| Test Voltage (two seconds): |
2500 VDC |
| |
|
| Capactior Class (EN133200): |
Designed to meet Y4 |
| |
|
| Pulse Test (EN133200): |
2500V Peak |
| |
|
Insulation Resistance
(within 1 minute): |
For C <0.33μF, R> 15000MΩ
For C>0.33μF, RC(MΩ*μF)>5000s |
| |
|
Operating Ambient Temperature Range
(@ rated current Ir): |
10 to 100 Amps: -40°C to +60°C
200 Amps: -40°C to +50°C
|
| |
|
| Category Temperature Range: |
-40°C to +85°C |
| |
|
| Climatic Category: |
40/85/21 |
| |
|
| MTBF: |
Typically > 5 million hours |
| |
|
| Case and Terminal Material / Finish: |
Nickel Plated Brass |
| |
|
| Insulating Materials Flammability Rating: |
UL 94V-0 |
| |
|
| Typical insertion loss in dB: |
| Line to ground in 50 ohm circuit |
|
| Capacitor ID |
Frequency - MHz |
| 0.01 |
0.03 |
0.1 |
0.3 |
1 |
10 |
100 |
1000 |
|
| CA |
- |
- |
2 |
4 |
10 |
23 |
65 |
100 |
| HB |
2 |
4 |
10 |
18 |
27 |
62 |
95 |
100 |
| HE |
2 |
4 |
10 |
18 |
27 |
67 |
95 |
100 |
| NC |
7 |
14 |
23 |
30 |
32 |
70 |
100 |
100 |
| ND |
7 |
14 |
23 |
30 |
32 |
70 |
100 |
100 |
| NH |
7 |
14 |
23 |
31 |
35 |
75 |
100 |
100 |
| PK |
14 |
21 |
30 |
34 |
53 |
75 |
100 |
100 |
| RP |
20 |
32 |
40 |
52 |
85 |
100 |
100 |
100 |
|
Current derating above ambient:
10-100 Amp: For temperature, θ Iθ = IR √ (85-θ)/25
200 Amp: For temperature, θ Iθ = IR √ (85-θ)/35
|
Case Styles
| T1 - Terminal Thread |
| Part Number(s) |
Thread |
Torque
(in-lb.) |
| 10FFD6-CA/HE |
M3 |
4 |
16FFD6-CA/HE
32FFD6-CA/HE |
M4 |
11 |
| 63FFD6-HB/NH |
M6 |
22 |
| 100FFD6-NC/PK |
M8 |
44 |
| 200FFD6-ND/RP |
M10 |
70 |
|
|
|
| T2 - Mounting Thread |
| Part Number(s) |
Thread |
Torque
(in-lb.) |
10FFD6-CA/HE
16FFD6-CA/HE
32FFD6-CA/HE |
M12 x 1 |
35 |
| 63FFD6-HB/NH |
M20 x 1 |
89 |
| 100FFD6-NC/PK |
M24 x 1 |
124 |
| 200FFD6-ND/RP |
M27 x 1.5 |
142 |
|
Case Dimensions
| Part
Number |
A |
B |
C |
D |
E |
F |
| ± .04 |
± .02 |
±.04 |
± .04 |
± .08 |
ref. |
| 1 |
0.5 |
1 |
1 |
2 |
| 10FFD6-CA |
3.54 |
0.79 |
1.93 |
0.47 |
0.63 |
0.67 |
| 90 |
20 |
49 |
12 |
16 |
17 |
16FFD6-CA
32FFD6-CA |
3.86 |
0.79 |
2.09 |
0.47 |
0.71 |
0.67 |
| 98 |
20 |
53 |
12 |
18 |
17 |
| 63FFD6-HB |
6.30 |
0.98 |
3.70 |
0.55 |
1.02 |
0.87 |
| 160 |
25 |
94 |
14 |
26 |
22 |
| 100FFD6-NC |
7.24 |
1.26 |
4.09 |
0.63 |
1.26 |
1.06 |
| 184 |
32 |
104 |
16 |
32 |
27 |
| 200FFD6-ND |
8.23 |
1.50 |
4.41 |
0.75 |
1.57 |
1.06 |
| 209 |
38 |
112 |
19 |
40 |
27 |
| 10FFD6-HE |
5.12 |
0.79 |
3.50 |
0.47 |
0.63 |
0.67 |
| 130 |
20 |
89 |
12 |
16 |
17 |
16FFD6-HE
32FFD6-HE |
5.47 |
0.79 |
3.70 |
0.47 |
0.71 |
0.67 |
| 139 |
20 |
94 |
12 |
18 |
17 |
| 63FFD6-NH |
6.81 |
1.26 |
4.13 |
0.63 |
1.02 |
1.06 |
| 173 |
32 |
105 |
16 |
26 |
27 |
| 100FFD6-PK |
8.98 |
1.50 |
5.71 |
0.75 |
1.26 |
1.06 |
| 228 |
38 |
145 |
19 |
32 |
27 |
| 200FFD6-RP |
10.98 |
2.13 |
7.17 |
0.75 |
1.57 |
1.57 |
| 279 |
54 |
182 |
19 |
40 |
40 |
Part Numbers