| Medical EMI Filters |
| MRI-2030R |
|

UL Listed 6P16 |
Catalog Data Sheet |
| Medical EMI Filter with Reduced Size and Cost 100db from 5MHz to 20GHz |
Features
- UL 1283 listed CSA Certified
- Filter compartment hermetically sealed, constructed of suitably plated steel
- Competitively priced
- Removable input cover for terminal access and field wiring connection
- Knockouts provided on the input side
- Threaded conduit fitting with flexible lead on the load side
- Discharge bleeder resistor provided to reduce shock hazard
Electrical Characteristics
| Voltage Drop: |
Less than 1% @ unity power factor |
| Overload: |
140% of rated current for 15 minutes |
| Harmonic Distortion: |
Less than 2% @ full current |
| Dielectric Withstanding Voltage: |
Per MIL-F-15733 and UL1283 |
| DC Insulation Resistance: |
Per MIL-STD-202, Method 302 |
| Terminal Strength: |
Per MIL-STD-202, Method 211, Condition E |
| Temperature Rise: |
Per MIL-F-15733 |
| R.F. Radiation |
100 dB minimum shielding effectiveness |
| Insertion Loss: |
100 db from 5MHz to 20GHz per MIL-STD-220A, under load condition |
| Rated Voltage: |
277/480 VAC |
| Operating Frequency: |
50/60 Hz |
| Rated Current |
2 x 30A |
|

|
MRI2030R Case Style and Dimensions
|
|
| MRI-2030 |

UL Listed 6P16
|
Catalog Data Sheet |
| High Performance Medical EMI Filter 100db from 100kHz to 10GHz |
Features
- UL 1283 listed
- Filter compartment hermetically sealed, constructed of 16 gauge suitably plated or painted steel
- Removable input cover for terminal access and field wiring connection
- Knockouts provided on the input side
- Threaded conduit fitting with flexible lead on the load side
- Discharge bleeder resistor provided to reduce shock hazard
Electrical Characteristics
| Voltage Drop: |
Less than 1% @ unity power factor |
| Overload: |
140% of rated current for 15 minutes |
| Harmonic Distortion: |
Less than 2% @ full current |
| Dielectric Withstanding Voltage: |
Per MIL-F-15733 and UL1283 |
| DC Insulation Resistance: |
Per MIL-STD-202, Method 302 |
| Terminal Strength: |
Per MIL-STD-202, Method 211, Condition E |
| Temperature Rise: |
Per MIL-F-15733 |
| R.F. Radiation |
100 dB minimum shielding effectiveness |
| Insertion Loss: |
100 db from 100 kHz to 10GHz per MIL-STD-220A, under load condition |
| Rated Voltage: |
277/480 VAC |
| Operating Frequency: |
50/60 Hz |
| Rated Current |
2 x 30A |
|

|
MRI2030 Case Style and Dimensions
|
| USA Customer Service: |
1-800-468-2023 |
| Corcom Products Direct: |
1-847-680-7400 |
| Germany: |
49-89-6089-0 |
|
Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change. |