| Stand-Alone, Capacitive Input |
|

UL Listed 6P16 |
Catalog Data Sheet |
Features
- Sealed, constructed of 16 gauge cold rolled steel
- All non-conductive surfaces protected with suitable painting or electro plating
- Removable input cover for terminal access and field wiring connection
- Knockouts provided on the input side
- Threaded conduit fitting with flexible lead on the load side
- Discharge bleeder resistor provided to reduce shock hazard
- Surge arrestors provided upon request
|

|
Electrical Characteristics
| Voltage Drop: |
Less than 1% @ unity power factor |
| Overload: |
140% of rated current for 15 minutes |
| Harmonic Distortion: |
Less than 2% @ full current |
| Dielectric Withstanding Voltage: |
Per MIL-F-15733 and UL1283 |
| DC Insulation Resistance: |
Per MIL-STD-202, Method 302 |
| Terminal Strength: |
Per MIL-STD-202, Method 211, Condition E |
| Temperature Rise: |
Per MIL-F-15733 |
| R.F. Radiation |
100 dB minimum shielding effectiveness |
| Insertion Loss: |
100 db from 14 kHz - 10GHz per MIL-STD-220A, under load condition Applicable Publications |
Applicable Publications
| MIL-F-15733 |
Filters, radio interference |
| MIL-STD-202F |
Test methods for Components |
| MIL-STD-220A |
Test method of Insertion Loss |
| MIL-STD-285 |
Test method for Shielding Effectiveness |
| NFPA 70-1987 |
National Electric Code |
| 486A-1983 |
Wire Connectors and Lug |
| UL 1283 |
Underwriters Laboratories |
|
How to Order

Note 1:
A6/A4* - Optional surge arrestors: V251BA60
B6 - Optional surge arrestors : V481BA60
Max. Operating Voltage
A6: |
120/208V |
60 Hz |
B6: |
277/480V |
60 Hz |
A4*: |
120/208V |
400 Hz |
*400Hz filters available upon request. Will require external power factor correction coil. Please contact Tyco Electronics Application Engineering at 847-573-6517
Click here for more information on power factor correction coils. |
CDSUW-C Case Style

|
Dimensions
| CDSUW |
# Filters x Current
(Amps) |
Dimensions |
Wire Gauge |
Approx.
Weight
|
| A |
B |
C |
D |
E |
F |
| ±.063 |
±.063 |
±.063 |
(ref.) |
(ref.) |
(ref.) |
AWG |
Lbs. |
| 1.6 |
1.6 |
1.6 |
mm² |
Kg |
|
| 1010**-C |
1 x 10 |
21.0 |
4.0 |
5.0 |
5.0 |
3.0 |
.31 x .50 |
10 |
15 |
| 533.4 |
101.6 |
127.0 |
127.0 |
76.2 |
7.87 x 12.7 |
5.26 |
6.80 |
| 2010**-C |
2 x 10 |
21.0 |
8.0 |
5.0 |
5.0 |
5.5 |
.43 x .75 |
10 |
30 |
| 533.4 |
203.2 |
127.0 |
127.0 |
139.7 |
10.9 x19.1 |
5.26 |
13.6 |
| 1030**-C |
1 x 30 |
26.0 |
6.0 |
6.0 |
5.0 |
4.0 |
.31 x .50 |
6 |
30 |
| 660.4 |
152.4 |
152.4 |
127.0 |
101.6 |
7.87 x 12.7 |
13.20 |
13.6 |
| 2030**-C |
2 x 30 |
26.0 |
12.0 |
6.0 |
5.0 |
9.0 |
.43 x .75 |
6 |
60 |
| 660.4 |
304.8 |
152.4 |
127.0 |
228.6 |
10.9 x 19.1 |
13.20 |
27.2 |
| 1060**-C |
1 x 60 |
32.0 |
8.0 |
6.0 |
6.0 |
5.5 |
.43 x .75 |
6 |
60 |
| 812.8 |
203.2 |
152.4 |
152.4 |
139.7 |
10.9 x 19.1 |
13.20 |
27.2 |
| 1100**-C |
1 x 100 |
34.0 |
8.0 |
6.0 |
8.0 |
5.5 |
.43 x .75 |
2 |
70 |
| 863.6 |
203.2 |
152.4 |
203.2 |
139.7 |
10.9 x 19.1 |
33.6 |
31.8 |
| 1150**-C |
1 x 150 |
41.0 |
10.0 |
6.0 |
9.0 |
9.0 |
.43 x.75 |
0 |
90 |
| 1041.4 |
254.0 |
152.4 |
228.6 |
228.6 |
10.9 x 19.1 |
53.5 |
40.8 |
| 1225**-C |
1 x 225 |
41.0 |
10.0 |
6.0 |
9.0 |
9.0 |
.43 x .75 |
250 MCM |
120 |
| 1041.4 |
254.0 |
152.4 |
228.6 |
228.6 |
10.9 x 19.1 |
126.0 |
54.4 |
|
|
| USA Customer Service: |
1-800-468-2023 |
| Corcom Products Direct: |
1-847-680-7400 |
| Germany: |
49-89-6089-0 |
|
Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change. |