Skip to content
Home > Series > Facility > CDSUA

CDSUA Series

Stand-Alone, Value Based

 

Catalog Data Sheet

Features

  • All four current ratings utilize a single housing (single-wire 30, 60 100A and two wire 30A)
  • Sealed using 18 AWG suitably plated housing
  • Removable input cover provides quick access to terminals
  • Three knockouts on the input side
  • Discharge bleeder resistor provided to reduce shock hazard
  • Surge protector provided upon request

Electrical Characteristics

Voltage Drop: Less than 1% @ unity power factor
Overload: 140% of rated current for 15 minutes
Harmonic Distortion: Less than 2% @ full current
Dielectric Withstanding Voltage: Per MIL-F-15733 and UL1283
DC Insulation Resistance: Per MIL-STD-202, Method 302
Terminal Strength: Per MIL-STD-202, Method 211, Condition E
Temperature Rise: Per MIL-F-15733
R.F. Radiation 100 dB minimum shielding effectiveness
Insertion Loss: 100 db from 100 kHz - 10GHz per MIL-STD-220A
Operating Frequency: 50/60 Hz
Operating Voltage: 277/480 VAC (max.)

Part Numbers

Part Nos. Current (Amps) Wire Gauge (AWG) # of wires

CDSUA1030-C 30 6 1
CDSUA1060-C 60 6 1
CDSUA1100-C 100 1 1
CDSUA2030-C 2 x 30 6 2

 

How to Order


CDSUA Case Style and Dimensions

 

USA Customer Service: 1-800-468-2023
Corcom Products Direct: 1-847-680-7400
Germany: 49-89-6089-0
Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change.