Skip to content
 |  Tyco Electronics Segment Indicator  |   | 
Tyco Electronics - Our commitment. Your advantage.
Visit www.tycoelectronics.com Corcom Products
Home > Series > Facility > CDEUL

CDEUL Series

NEMA Cabinet Style, Extended Range Buffer Network- Inductive Input


UL Listed 6P16

Catalog Data Sheet

Filter Cabinet

  • Modified NEMA I, constructed of not less than #14 gauge CRS with galvanized steel bulkhead
  • Finish: Blue epoxy to all non-conductive surfaces
  • R.F. Radiation of the shielded (load) compartment shall be greater than 100dB from 14kHz to 10GHz
  • Front cover access, dual cover design
  • Prewired standoffs and lugs
  • Lifting hooks and mounting tabs
  • Hubs and penetration installed upon request
  • Legs for floor mount available

Individual Filters

  • Hermetically sealed components with welded and/or soldered seams
  • Constructed of not less than # 16 gauge steel with corrosion resistant plating
  • Bleeder resistor to eliminate shock hazard provided
  • HEMP surge arrestors provided upon request (Current ratings to 800A)


Shown with optional 12" legs

Electrical Characteristics

Voltage Drop: Less than 1% @ unity power factor
Overload: 140% of rated current for 15 minutes
Harmonic Distortion: Less than 2% @ full current
Dielectric Withstanding Voltage: Per MIL-F-15733 and UL1283
DC Insulation Resistance: Per MIL-STD-202, Method 302
Terminal Strength: Per MIL-STD-202, Method 211, Condition E
Temperature Rise: Per MIL-F-15733
R.F. Radiation 100 dB minimum shielding effectiveness
Insertion Loss: 100 db from 14 kHz - 10GHz per MIL-STD-220A, under load condition, using extended range buffer networks over the frequency range of 14 kHz - 20 MHz

Applicable Publications

MIL-F-15733 Filters, radio interference
MIL-STD-202F Test methods for Components
MIL-STD-220A Test method of Insertion Loss
MIL-STD-285 Test method for Shielding Effectiveness
NFPA 70-1987 National Electric Code
486A-1983 Wire Connectors and Lug
UL 1283 Underwriters Laboratories

 

How to Order

Note 1:
A6/A4* - Optional surge arrestors: V251BA60
B6 - Optional surge arrestors : V481BA60

Max. Operating Voltage

A6:
120/208V
60 Hz
B6:
277/480V
60 Hz
A4*:
120/208V
400 Hz

*400Hz filters available upon request. Will require external power factor correction coil. Please contact Tyco Electronics Application Engineering at 847-680-7400 x517.

Click here for more information on power factor correction coils.

CDEUL Case Style

Dimensions

# Filters x Current
(Amps)
A B C D E

Approx.
Weight
(Lbs/Kg)


2 x 10 14.0 30.0 6.0 22.0 16.0 95
355.6 762.0 152.4 558.8 406.4 43.1
3 x 10 20.0 30.0 6.0 22.0 22.0 100
508.0 762.0 152.4 558.8 406.4 45.4
4 x 10 26.0 30.0 6.0 22.0 28.0 120
660.4 762.0 152.4 558.8 711.2 54.4

2 x 30 16.0 38.0 8.0 26.0 18.0 170
406.4 965.2 203.2 660.4 457.2 77.1
3 x 30 23.0 38.0 8.0 26.0 25.0 240
584.2 965.2 203.2 660.4 635.0 108.9
4 x 30 30.0 38.0 8.0 26.0 32.0 300
762.0 965.2 203.2 660.4 812.8 136.1

2 x 60 & 100 16.0 44.0 10.0 32.0 18.0 240
406.4 1117.6 254.0 812.8 457.2 108.9
3 x 60 & 100 23.0 44.0 10.0 32.0 25.0 310
584.2 1117.6 254.0 812.8 635.0 140.6
4 x 60 & 100 30.0 44.0 10.0 32.0 32.0 400
762.0 1117.6 254.0 812.8 812.8 181.4

2 x 150 16.0 54.0 14.0 42.0 18.0 320
406.4 1371.6 355.6 1066.8 457.2 145.1
3 x 150 23.0 54.0 14.0 42.0 25.0 430
584.2 1371.6 355.6 1066.8 635.0 195.0
4 x 150 30.0 54.0 14.0 42.0 32.0 650
762.0 1371.6 355.6 1066.8 812.8 294.8

2 x 225 16.0 54.0 14.0 42.0 18.0 380
406.4 1371.6 355.6 1066.8 457.2 172.4
3 x 225 23.0 54.0 14.0 42.0 25.0 520
584.2 1371.6 355.6 1066.8 635.0 235.9
4 x 225 30.0 54.0 14.0 42.0 32.0 700
762.0 1371.6 355.5 1066.8 812.8 317.5

2 x 300 & 400 22.0 64.0 26.0 61.5 24.0 800
558.8 1625.6 660.4 1562.1 609.6 362.9
3 x 300 & 400 30.0 64.0 26.0 61.5 32.0 1100
762.0 1625.6 660.4 1562.1 812.8 498.9
4 x 300 & 400 38.0 64.0 26.0 61.5 40.0 1400
965.2 1625.6 660.4 1562.1 1016.0 635.0

2 x 600 & 800 38.0 70.0 26.0 67.5 40.0 1400
965.2 1778.0 660.4 1714.5 1016.0 635.0
3 x 600 & 800 56.0 70.0 26.0 67.5 58.0 2100
1422.4 1778.0 660.4 1714.5 1473.2 952.5
4 x 600 & 800 72.0 70.0 26.0 67.5 74.0 2600
1828.8 1778.0 660.4 1714.5 1879.6 1179.3

2 x 1000 & 1200 56.0 70.0 26.0 67.5 58.0 2000
1422.4 1778.0 660.4 1714.5 1473.2 907.2
3 x 1000 & 1200 82.0 70.0 26.0 67.5 84.0 3000
2082.8 1778.0 660.4 1714.5 2133.6 1360.8
4 x 1000 & 1200 106.0 70.0 26.0 67.5 108.0 3800
2692.4 1778.0 660.4 1714.5 2743.2 1723.6

 

USA Customer Service: 1-800-468-2023
Corcom Products Direct: 1-847-680-7400
Germany: 49-89-6089-0
Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change.