AYC Series
The AYC series filters are designed for 3-phase, four-wire,WYE wiring applications. These cost-effective filters help better protect electronic equipment in industrial applications.
The series offers filtering up to 180 amps maximum and is used in 3-phase, noisy industrial applications such as frequency converters. The AYC series is designed to comply with International Standards including EN133200 and UL 1283.
Electrical Schematic

Resistor location for reference only |
Specifications
| Maximum leakage current, each line to ground: |
| |
@ 120 VAC 60 Hz: |
|
| |
16A |
62mA |
| |
25/36A |
68mA |
| |
63/80/110/150A |
74mA |
| |
180A |
111mA |
| |
@ 250 VAC 50 Hz: |
|
| |
16A |
106mA |
| |
25/36A |
118mA |
| |
63A |
128mA |
| |
80/110/150A |
129mA |
| |
180A |
192mA |
| |
|
|
| Hipot rating (one minute): |
| |
line to ground |
1850VDC |
| |
line to line |
1850VDC |
| |
line to neutral |
1450VDC |
| |
|
|
| Operating Frequency: |
50 / 60 Hz |
| |
|
|
| Rated voltage (max.): |
480 VAC |
| |
|
|
| Rated Current: |
16A to 180A * |
| |
* refer to part number for rating |
| Minimum insertion loss in dB: |
| Line to ground in 50 ohm circuit |
|
| Current Rating |
Frequency - MHz |
| .01 |
.05 |
.1 |
.5 |
1 |
5 |
10 |
30 |
|
| 16A |
23 |
66 |
82 |
88 |
82 |
79 |
55 |
21 |
| 25A |
26 |
68 |
83 |
93 |
88 |
68 |
45 |
4 |
| 36A |
18 |
61 |
78 |
96 |
91 |
71 |
49 |
7 |
| 63A |
11 |
57 |
72 |
90 |
86 |
68 |
44 |
4 |
| 110A |
10 |
51 |
60 |
88 |
84 |
74 |
50 |
12 |
| 150A* |
0 |
50 |
57 |
82 |
79 |
75 |
51 |
7 |
| 150A |
1 |
51 |
55 |
85 |
82 |
84 |
51 |
11 |
| 180A |
3 |
53 |
55 |
97 |
89 |
81 |
56 |
20 |
|
| Line to line in 50 ohm circuit |
|
| Current Rating |
Frequency - MHz |
| .01 |
.05 |
.1 |
.5 |
1 |
5 |
10 |
30 |
|
| 16A |
21 |
32 |
54 |
90 |
86 |
73 |
72 |
47 |
| 25A |
23 |
33 |
60 |
100 |
95 |
87 |
70 |
38 |
| 36A |
25 |
37 |
51 |
94 |
87 |
69 |
58 |
17 |
| 63A |
27 |
45 |
41 |
84 |
77 |
63 |
61 |
43 |
| 110A |
27 |
35 |
39 |
75 |
72 |
51 |
44 |
31 |
| 150A* |
28 |
37 |
42 |
74 |
67 |
52 |
45 |
30 |
| 150A |
28 |
40 |
42 |
73 |
66 |
51 |
44 |
31 |
| 180A |
30 |
41 |
50 |
70 |
64 |
49 |
42 |
26 |
|
| * 150AYC10B-95 model only |
|
Case Styles
16, 25, 36, 63 AYC10B

80, 110 ,150 AYC10B / -95

180AYC10B

|
Case Dimensions
| Part No. |
A |
B |
C |
D |
E |
| (max.) |
(max.) |
(max.) |
(max.) |
± .078 |
| ± .2 |
| 16AYC10B |
6.69 |
4.37 |
2.56 |
4.92 |
2.76 |
| 170.0 |
111.0 |
65.0 |
125.0 |
70.0 |
|
| 25AYC10B |
9.96 |
5.08 |
2.52 |
5.71 |
4.53 |
| 246.0 |
129.0 |
64.0 |
145.0 |
115.0 |
|
| 36AYC10B |
10.35 |
5.08 |
2.52 |
5.71 |
4.53 |
| 263.0 |
129.0 |
64.0 |
145.0 |
115.0 |
|
| 63AYC10B |
10.89 |
5.08 |
2.52 |
5.71 |
4.53 |
| 279.0 |
129.0 |
64.0 |
145.0 |
115.0 |
|
80/110/150
AYC10B |
12.09 |
5.55 |
5.55 |
6.10 |
4.53 |
| 307.0 |
141.0 |
141.0 |
155.0 |
115.0 |
|
| 180AYC10B |
15.71 |
5.55 |
5.55 |
6.10 |
3.25 |
| 399.0 |
141.0 |
141.0 |
155.0 |
82.5 |
|
Terminals
| |
|
Type (qty.) |
Torque in. lb. |
| 16AYC10B |
| GroundTerminals |
|
M5 (2) |
26 max. |
| Phoenix Contacts |
|
VDFK4 (8) |
5.31 min. |
| Accepts 12 AWG stranded wire. Strip length 0.315 |
|
| 25AYC10B |
| Ground Terminals |
|
M5 (2) |
26 max |
| Phoenix Contacts |
|
VDFK6 (8) |
13.28 min. |
| Accepts 10 AWG stranded wire. Strip length 0.354 |
|
| 36AYC10B |
| Ground Terminals |
|
M5 (2) |
26 max. |
| Phoenix Contacts |
|
HDFK10 (8) |
13.28 min |
| Accepts 8 AWG stranded wire. Strip length 0.433 |
|
| 63AYC10B |
| Ground Terminals |
|
M6 (2) |
53 max. |
| Phoenix Contacts |
|
HDFK16 (8) |
17.70 min. |
| Accepts 6 AWG stranded wire. Strip length 0.630 |
|
| 80/110/150 AYC10B |
| Terminals |
|
M10 (2) |
58 max |
| Phoenix Contacts |
|
HDFK50 (8) |
53.10 min |
| Accepts 1 AWG stranded wire. Strip length 0.945 |
|
| 150AYC10B-95 / 180AYC10B |
| Ground Terminasl |
|
M10 (2) |
58 max |
| Phoenix Contacts |
|
HDFK95 (8) |
132 min |
| Accepts 0 AWG stranded wire. Strip length 1.063 |
|
Part Numbers
Click on any part number for distributor stock status and eCommerce Links. For more information refer to the Corcom Part Numbering System reference.
|